3 hp VFD, Single Phase to Three Phase VFD

Low price 3hp VFD, convert 220V/230V/240V 1 phase to 3 phase variable frequency drive, 10amps, RS485 enabled, manufacturer direct sale.
Free shipping
Delivery date: 6 - 12 Days
$279.68
$238.14

3hp variable frequency drive, single phase 220V to three phase VFD, 10 amps.

Specification:

Basics Model GK3000-2S0022
Capacity 3 hp (2.2 kW)
Shipping weight 3 kg
Dimension 184*98*135 mm
I/O Feature Rated current 10 A
Input voltage 1 phase 220~240V AC
Input frequency 50Hz/ 60Hz
Output voltage 3 phase AC 0~input voltage
Output frequency 0.00~400.00Hz
Over load capacity 150% of rated current for 1 minute, 180% of rated current for 3 seconds
Control Feature Control mode V/F control;
Sensorless vector control;
Communication RS485
Speed regulation 1:100
Start torque 150% of rating torque at 1 Hz
Speed control accuracy ≤±0.5% of rating synchronous speed
Frequency precision Digital setting: max frequency x± 0.01%;
Analog setting: max frequency x± 0.2%
Frequency resolution Analog setting: 0.1% of max frequency;
Digital setting: 0.01Hz
Torque boost Automatic torque boost, manual torque boost 0.1%~30.0%
Interior PID controller Be convenient to make closed-loop system
Automatic energy save running Optimize V/F curve automatically based on the load to realize power save running
Automatic voltage regulation (AVR) Can keep constant output voltage when power source voltage varies.
Automatic current limiting Limit running current automatically to avoid frequent over-current which will cause trip
Environment Enclosure rating IP 20
Temperature –10℃~ +40℃; VFD will be derated if ambient temperature exceed 40℃; each rise 1℃, the derate will be 5%
Humidity 5%-95%, without condensation
Altitude ≤1000m; VFD will be derated if above 1000m
Impingement and oscillation Normal running:<5.9m/s2 (0.6g); Transportation:<15m/s2 (1.5g)
Store environment –20℃~ +60℃; no dust, no corrosive gas, no direct sunlight

 

Tips: Why AFE VFD costs more?
The basic issues with using an AFE (active front end, low harmonic variable frequency drive) are cost and complexity. The cost of the VFD is typically 50 to 100% more than a standard 6 pulse VFD and the complexity (read that as reliability) of the VFD also goes up. An AFE drive replaces the standard diode bridge with IGBTs which not only add components but also requires more processor power. To add insult to injury, the top end of the VFD will have to include an LCL filter which adds more to the cost. Low harmonic multi-pulse front ends require a phase shifting transformer as well as extra diode bridges.

Download PDF, DOC...
PDF: GK3000 VFD User Manual
Write your own review for 3 hp VFD, Single Phase to Three Phase VFD
  • Only registered users can write reviews
Needs Improvement Best

Existing reviews

1-phase to 3-phase
This is very good input for us and our customer in choosing way in a newly started project with 1-phase power supply.
By Colin on 27/04, 2018
Was this review helpful? Yes / No (0/0)
Distance
For your 1-phase To 3-phase motor drive, the distance from the Control Center to the pump is about 35 meters. The pump has a 2.25 kW (3 Horsepower) motor. Is that distance within the operating limits of application of the VFD?
By Amy on 12/02, 2020
Was this review helpful? Yes / No (0/0)
Distance
Yes, its okay for 35m distance.
By GoHz.com on 12/02, 2020
Was this review helpful? Yes / No (1/0)
i have a question about this vfd
if im going to run this vfd on 3HP 3 phase 2 Pole and 50hz from the input 220va ac which grid ok so now tell me how much amps it will take from my grid to full load the motor?
By roxan on 25/06, 2020
Was this review helpful? Yes / No (0/0)